Temperature sensors must be inserted all the way to the bottom of the containers. If
a short period of response is required, a non-setting heat conductive paste may be
used.
Insert the plastic case of the sensor cable into the sensor container, and fasten the
cable with the supplied M4 screw, which has an opening for a sealing wire. The
screw is only to be tightened with your fingers. Seal the containers using the seal and
wire.
2.2 Short direct temperature sensors
Short direct sensors can be mounted into special ball valves or special T-parts. Both
contain threads up to the R1 size, and a built-in M10 clutch for a short direct sensor.
For assembly into existing heating installations equipped with standard T-shaped
branches, the Kamstrup A/S Company is able to supply brass inserts of R½ and R¾
size, suitable for short direct sensors.
Short direct sensors can also be installed directly into all ULTRAFLOW
®
machine
versions, with G¾ and G1 threads, on the flow parts of the meter. Fasten the brass
sensor inserts lightly (to ca 4 Nm), using a 12 mm wrench, and seal the sensors with
seal and wire.